Start your 7-day free trial — no credit card required. Get started →
No more extracting test requirements by hand. Upload your plans and specs, get an audit-ready ITP in minutes.
3.6 FIELD QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency.
B. Concrete Tests:
1. Sampling Fresh Concrete: ASTM C172
2. Slump: ASTM C143/C143M
3. Air Content: ASTM C231, pressure method
4. Compressive Strength: ASTM C39/C39M
a. Cast and cure three standard cylinders
b. Test one cylinder at 7 days
c. Test two cylinders at 28 days
5. Temperature: ASTM C1064 at point of delivery
C. Tolerances:
1. Slab thickness: +3/8 in., -1/4 in.
2. Horizontal alignment: ±1/2 in. in 10 ft
3. Vertical alignment: ±1/4 in. in 10 ft
D. Curing Requirements:
1. Maintain 50°F minimum for 7 days
2. Moisture cure per ACI 308.13.4 FIELD QUALITY CONTROL A. Grading and Fill Tests: 1. Proctor Density: ASTM D1557 Modified 2. In-place Density: ASTM D6938 Nuclear Method 3. Minimum compaction: 95% of max dry density B. Testing Frequency: 1. Every 2-foot lift of fill 2. Every 500 square feet of subgrade 3. At each change of material source C. Subgrade Preparation: 1. Proof-roll with loaded dump truck 2. Remove soft spots and replace with structural fill 3. Scarify and recompact to 6-inch depth D. Acceptance Criteria: 1. No pumping or rutting under proof-roll 2. Density tests within specified range
3.3 FIELD QUALITY CONTROL A. Special Inspection per IBC Chapter 17. B. Welding Inspection: 1. Visual: AWS D1.1 all welds 2. Ultrasonic: ASTM E164 for CJP welds 3. Magnetic Particle: ASTM E709 C. Bolt Inspection: 1. Pre-installation verification per RCSC 2. Pretensioned: calibrated wrench or DTI 3. Slip-critical: Faying surfaces clean, dry D. Tolerances per AISC Code of Standard Practice: 1. Column plumbness: 1/500 of height 2. Beam sweep: L/1000 3. Elevation: ±3/4 in. from theoretical E. Fireproofing inspection after steel erection
3.10 WATER SYSTEM TEST A. Fill piping with water and purge air. B. Test pressure: 150 psi minimum for 2 hours. C. No leakage permitted. Repair and retest. 3.14 DWV TESTING A. Air Test: 5 psi gauge for 15 minutes. B. Water Test: 10-foot head for minimum 15 min. C. Inspect joints for leaks with detector. 3.16 STORM DRAINAGE TEST A. Flood test each horizontal drain for 15 min. B. No leakage at joints or connections. C. Verify proper slope: 1/4 in. per foot minimum D. Video inspection of underground mains 1. Record location of all connections 2. Document pipe condition and alignment
3.03 TESTING AND INSPECTION A. Insulating Resistance Testing: 1. Megger test on each circuit at 500V DC 2. Duration: one minute minimum 3. Record readings for each circuit B. Operating Test: 1. Demonstrate operation of each system 2. Verify proper phase rotation 3. Test ground fault protection devices C. Grounding System: 1. Test electrode resistance: 5 ohms maximum 2. Verify bonding at all connections 3. Document with calibrated earth ground tester D. Emergency Power: 1. Transfer switch: 10-second maximum 2. Load bank test: 4 hours at rated capacity
3.4 FIELD QUALITY CONTROL A. Adhesion Testing: 1. Field adhesion test per ASTM C1521 2. Test three locations per elevation 3. Minimum: 100% cohesive failure B. Inspection: 1. Verify joint preparation prior to sealant 2. Check backer rod depth and diameter 3. Document ambient conditions C. Environmental Requirements: 1. Temperature: 40°F to 100°F 2. No rain within 24 hours of application 3. Surfaces must be dry and frost-free D. Quality Records: 1. Log sealant batch numbers per location 2. Photograph joints before and after sealing
3.6 FIELD QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency.
B. Concrete Tests:
1. Sampling Fresh Concrete: ASTM C172
2. Slump: ASTM C143/C143M
3. Air Content: ASTM C231, pressure method
4. Compressive Strength: ASTM C39/C39M
a. Cast and cure three standard cylinders
b. Test one cylinder at 7 days
c. Test two cylinders at 28 days
5. Temperature: ASTM C1064 at point of delivery
C. Tolerances:
1. Slab thickness: +3/8 in., -1/4 in.
2. Horizontal alignment: ±1/2 in. in 10 ft
3. Vertical alignment: ±1/4 in. in 10 ft
D. Curing Requirements:
1. Maintain 50°F minimum for 7 days
2. Moisture cure per ACI 308.13.4 FIELD QUALITY CONTROL A. Grading and Fill Tests: 1. Proctor Density: ASTM D1557 Modified 2. In-place Density: ASTM D6938 Nuclear Method 3. Minimum compaction: 95% of max dry density B. Testing Frequency: 1. Every 2-foot lift of fill 2. Every 500 square feet of subgrade 3. At each change of material source C. Subgrade Preparation: 1. Proof-roll with loaded dump truck 2. Remove soft spots and replace with structural fill 3. Scarify and recompact to 6-inch depth D. Acceptance Criteria: 1. No pumping or rutting under proof-roll 2. Density tests within specified range
3.3 FIELD QUALITY CONTROL A. Special Inspection per IBC Chapter 17. B. Welding Inspection: 1. Visual: AWS D1.1 all welds 2. Ultrasonic: ASTM E164 for CJP welds 3. Magnetic Particle: ASTM E709 C. Bolt Inspection: 1. Pre-installation verification per RCSC 2. Pretensioned: calibrated wrench or DTI 3. Slip-critical: Faying surfaces clean, dry D. Tolerances per AISC Code of Standard Practice: 1. Column plumbness: 1/500 of height 2. Beam sweep: L/1000 3. Elevation: ±3/4 in. from theoretical E. Fireproofing inspection after steel erection
3.10 WATER SYSTEM TEST A. Fill piping with water and purge air. B. Test pressure: 150 psi minimum for 2 hours. C. No leakage permitted. Repair and retest. 3.14 DWV TESTING A. Air Test: 5 psi gauge for 15 minutes. B. Water Test: 10-foot head for minimum 15 min. C. Inspect joints for leaks with detector. 3.16 STORM DRAINAGE TEST A. Flood test each horizontal drain for 15 min. B. No leakage at joints or connections. C. Verify proper slope: 1/4 in. per foot minimum D. Video inspection of underground mains 1. Record location of all connections 2. Document pipe condition and alignment
3.03 TESTING AND INSPECTION A. Insulating Resistance Testing: 1. Megger test on each circuit at 500V DC 2. Duration: one minute minimum 3. Record readings for each circuit B. Operating Test: 1. Demonstrate operation of each system 2. Verify proper phase rotation 3. Test ground fault protection devices C. Grounding System: 1. Test electrode resistance: 5 ohms maximum 2. Verify bonding at all connections 3. Document with calibrated earth ground tester D. Emergency Power: 1. Transfer switch: 10-second maximum 2. Load bank test: 4 hours at rated capacity
3.4 FIELD QUALITY CONTROL A. Adhesion Testing: 1. Field adhesion test per ASTM C1521 2. Test three locations per elevation 3. Minimum: 100% cohesive failure B. Inspection: 1. Verify joint preparation prior to sealant 2. Check backer rod depth and diameter 3. Document ambient conditions C. Environmental Requirements: 1. Temperature: 40°F to 100°F 2. No rain within 24 hours of application 3. Surfaces must be dry and frost-free D. Quality Records: 1. Log sealant batch numbers per location 2. Photograph joints before and after sealing
Stage 01 · Upload & Receive
Drop in plans and specs as PDFs — up to 1,000+ pages. SpecFunnel reads your contract documents and extracts every project-specific testing requirement into an ITP log, organized by CSI division. What used to take 40–100 hours happens in minutes — ready for your team to review, adjust, and own.
Stage 02 · Track
Upload the test report PDF and SpecFunnel's AI extracts the results, inspector, location, and spec reference — you just verify everything looks right. Each report lands in one unified testing log, organized by CSI division, with compliance rates and subcontractor performance updating in real time. Audit-ready from day one.
Stage 03 · Export
Export your ITP log — or the complete package of organized test reports behind it — to PDF or Excel with your logo and company colors. Drop it straight into a submittal package or owner report — no reformatting required.
Before → After
Before
After
Scheduling
When the jobsite shifts, grab an inspection and drop it on a new day. The whole team sees the update instantly — no group text, no email chain.
Field supers, labs, and GC reps all see the same real-time calendar. Every inspection, every assignment, every change — in one place.
Send a one-click email request — inspectors accept or decline straight from their inbox. No login, no onboarding, no friction for the people doing the work.
Try It Yourself
Click through real construction data — no sign-up required. This is what your project looks like inside SpecFunnel.
Ready to try it with your own specs?
Start Free TrialTry It Yourself
This is what your project looks like inside SpecFunnel. Open on desktop to click through the full interactive demo.

FAQ
Talk to Us
See how SpecFunnel takes you from specs to scheduled, tracked inspections — all in one platform.